Chili is the latest heating circulator for closed systems in the Unistat product family. The compact heating thermostat is equipped with the E-grade Professional as standard and convinces with excellent thermodynamic properties and a range of functions for the highest demands. Chili guarantees highly accurate, reproducible temperature control results with short heat-up times and wide temperature ranges without changing fluids. Like all Unistats, the Chili is equipped with the innovative Pilot ONE controller with 5.7" touch screen and convenient menu navigation.
The economically Unistat technology provides minimized operating costs and efficient energy management. A further advantage is the extended life-time of the thermofluid. The hydraulically sealed systems prevent the formation of oil vapours and oxidation. Chili is the smallest heating thermostat in the Huber product range that is approved for use with Marlotherm as a thermofluid. For controlled cooling, an external cooling coil (unregulated) is available as an optional accessory. Due to ist technical properties and low purchase price, Chili is ideally suited for distillation tasks in botanical extraction, for example.
General information & temperature controller
Temperature range |
65...300 °C |
Temperature stability |
±0.02 °C |
Temperature control |
TAC, self-optimizing (True Adaptive Control) |
Display resolution |
0.01 °C |
Alarm message |
optical, acoustical  |
Controller |
Pilot ONE  (E-grade "Professional") |
Safety class |
III / FL Â |
Protection class |
IP20 Â |
Dimensions (W x D x H) |
240 x 427 x 393 mm  |  9.45 x 16.81 x 15.47 inches |
Weight |
23 kg  |  50.72 pounds |
Â
Heating / cooling capacity
Heating capacity |
2,7 - 3 Â kW |
Â
Circulation pump
Pressure pump max. |
45 lpm ; 0.9 bar  |  11.89 gpm ; 13.05 psi |
Pump connection |
M24x1,5 AG male  |
Permissible viscosity |
50 mm²/s |
Pump speed adjustable |
Yes |
Â
Connections
Pt100 connection |
Pt100 Â |
Control input |
0 Â |
Control output (potential-free) |
0 Â |
Analogue input |
via optional Com.G@te |
Analogue output |
via optional Com.G@te |
Digital interface |
RS232, Ethernet, USB Device, USB Host |
Â
Operating data
Permissible ambient temp. |
5...40 °C |
Filling volume min. |
1.45 Liters  |  0.38 gal |
Volume of expansion |
2 Liters  |  0.53 gal |
Power supply |
200-240V 1~/2~ 50/60Hz   |
Current max. |
15,5Â A |
Fusing |
16 A |