Huber Unichillers offer better efficiency, stable pressure and delivery performance with a constant cooling water temperature compared to traditional tap water cooling.
Chillers also reduce water consumption and help conserve the environment whilst lowering operating costs.
Unichillers are suitable for the removal of heat from chemical processes, cooling technical plants or as a central cooling water supply for laboratories.
All Unichillers are designed for continual operation at ambient temperatures up to +40°C. Installation in an outside areas is possible with optional weather protection and winter operation packages. Pumps are available with an extended pressure and flow rate for applications with a high pressure drops.
General information & temperature controller
Temperature range |
-20...100 °C |
Temperature stability |
±0.2 °C |
Temperature display |
OLED Display  |
Display resolution |
0.1 °C |
Alarm message |
optical, acoustical  |
Controller |
OLÉ |
Safety class |
III / FL Â |
Protection class |
IP20 Â |
Dimensions (W x D x H) |
350 x 496 x 622 mm  |  13.78 x 19.53 x 24.49 inches |
Weight |
60 kg  |  132.3 pounds |
Â
Heating / cooling capacity
Heating capacity |
1,6 - 2 Â kW |
Cooling capacity |
15 |
0 |
-10 |
-20 |
 °C |
1,5 |
1 |
0,7 |
0,3 |
 kW |
|
Cooling machine |
water-cooled  |
Refrigerant (ASHRAE, GHS) |
R449A (A1, H280) |
Â
Circulation pump
Pressure pump max. |
29 lpm ; 1 bar  |  7.66 gpm ; 14.5 psi |
Pump connection |
G3/4 AG male |
Â
Connections
Digital interface |
USB (Device), RS232 interfaces |
Â
Operating data
Permissible ambient temp. |
5...40 °C |
Noise level |
54Â dB(A) |
Filling volume min. |
3.8 Liters  |  1 gal |
Volume of expansion |
1.7 Liters  |  0.45 gal |
Cooling water connection |
G1/2 AG Â |
Cooling water consumption |
36Â l/h |
Cooling water differential pressure min. |
3 bar  |  43.5 psi |
Cooling water pressure max. |
6 bar  |  87 psi |
Power supply |
208-230V 1~/2~ 60Hz |